101 Totalisers
GENERAL SPECIFICATIONS
| Display | : Large LCD 40mm x 90mm, with seven 17mm and eleven 8mm digits. |
| Control Buttons | : Three touch buttons on U.V. resistant polyester key pad. |
| Casing | : High Impact, U.V. resistant, flameproof ABS – IP 66 case. |
| Dimensions | : 130mm x 114mm x 71mm ( L x H x D ). |
| Operating Temperature | : - 20°C to +70°C. |
| Configuration | :Configuration is done at SET UP level. |
| Password | : All settings can be password protected. |
| Data Protection | : EEPROM back up of all settings. Accumulated Total backed up every minute. |
| Input Frequency | : 0.01 Hz to 10 kHz. |
| Selectable Units | : TOTAL : L, GAL, bbl ( barrels ), m3, kg, lb or no unit in 0.67" digits. |
| : FLOWRATE : L, GAL, bbl ( barrels ), cf, m3, kg, lb or no unit in 0.32" digits | |
| :TIME UNITS : / second, / minute, / hour or / day . | |
| Tag Number | :A seven digit identification number can be entered for Screen notification |
| Environment | :EMC compliant ref : EN50081 and EN50082. |
Models
101 Totaliser and Flow rate Indicator
| Features: | Totaliser and Flow Rate indication with Linearisation |
| Power: | 3 V Lithium Battery ( average life 5 years ), although an 8 –
28 V D.C. supply can be connected. |
| Information: | Total , Flow Rate , Accumulated Total and measurement units. # Total can be reset to zero. Accumulated Total is not resettable. |
| 101 I Suitable for Hazardous Area Installation . Eex ia IIC T4 . |
101 a Totaliser and Flow Rate Indicator with Analogue and Pulse output
| Features: | Totaliser and Flow Rate indication with Linearisation. |
| Power: | 3 V Lithium Battery (average life 5 years ), although an 8 – 28
V A.C. / D.C. supply or 4 – 20 mA loop ( 28 V max ) can be connected. |
| Information: | Total, Flow Rate, Accumulated Total and measurement units. # Total can be reset to zero. Accumulated Total is not resettable. |
| 101 ai Suitable for Hazardous Area Installation. Eex ia IIB T4. |
101 b Totaliser and Batch Controller with Pulse output
This Batch Controller is a straight forward device offering exactly what is
required for the majority of applications. The operator can enter a reset
batch value easily or execute repeated batches. During the batch run, the
preset batch value is displayed as well as the batched quantity and units
of measurement . An overrun correction ensures an accurate batch quantity.
The running batch quantity ( 0.67" digits ) can be set to count up or
down. Two transistor outputs are available for either 1) pulse output and
one stage batch control or 2) two stage batch control.
| Features: | Preset Batch Value indication. |
| Power: | 3 V Lithium Battery ( average life 5 years ), although an 8 –
28 V A.C. / D.C. supply can be connected. |
| Information: | Preset Batch Value, Quantity Batched, Total, Accumulated Total and measurement units. # Total can be reset to zero. Accumulated Total is not resettable. |
| 101 bi Suitable for Hazardous Area Installation. Eex ia IIB T4. |
101 c Totaliser and Flow Rate Indicator with Critical Alarm output
| Features: | Totaliser and Flow Rate indication. |
| Power: | 3 V Lithium Battery ( average life 5 years ), although an 8 –
28 V A.C. / D.C. supply can be connected. |
| Information: | Total, Flow Rate, Accumulated Total, Alarm Points and measurement units. # Total can be reset to zero. Accumulated Total is not resettable. |
| 101 ci Suitable for Hazardous Area Installation . Eex ia IIB T4 . |
101 d Totaliser , Flow Rate and Direction of Flow Indicator
| Features: | Totaliser and Flow Rate indication. |
| Power: | 3 V Lithium Battery ( average life 5 years ), although an 8 –
28 V A.C. / D.C. supply can be connected. |
| Information: | Total, Flow Rate, Accumulated Total, Flow Direction and measurement
units. # Total can be reset to zero. Accumulated Total is not resettable. |
| 101 di Suitable for Hazardous Area Installation . Eex ia IIB T4 . |
Options
| PS: | 80 – 230 V A.C. Power Supply |
| MC: | Modbus Communication RS 485 |
Ordering
Order code: Model/ (Option)
e.g. 101a / PS